Aluminum coil and sheet for insulation jacketing: gauge, alloy and format
Insulation on industrial piping, tanks and equipment is protected by an aluminum jacket that shields it from rain, sun and impact. ASTM C1729 covers it in 3003 or 3105, 1100, 3004 and 5052 (National Insulation Association, April 2017), with minimum thicknesses from 0.016 to 0.040 in according to the insulation diameter (ITW, 2015). Almexa rolls plain coil and sheet in those alloys from 0.0177 in (0.45 mm) and up to 48 in (1,219 mm) wide, cast and rolled in Mexico: it covers gauges from 0.020 in up, for jacketing fabricators and for contractors who jacket tanks and equipment (technical sheet, October 2026).
Updated 2026-11-24

- Alloys
- 3003, 3105, 1100, 3004 and 5052
- Thickness at Almexa
- 0.0177 to 0.148 in: gauges from 0.020 in up
- Width
- 6.30 to 48 in; 5052 up to 36 in
- Finish
- Plain mill finish, no moisture barrier
The jacket, also called cladding, is the sheet that goes over the insulation. ASTM C1729 classifies it by three things: outer finish and emittance (Type), alloy and temper per ASTM B209 (Grade) and moisture barrier (Class). On piping the barrier is mandatory and must be heat laminated at the factory; elsewhere it is recommended (NIA, April 2017).
What gauge of aluminum is used for insulation jacketing?
| Insulation outside diameter | Rigid insulation | Non-rigid insulation |
|---|---|---|
| Up to 8 in | 0.016 in (0.41 mm) | 0.016 in (0.41 mm) |
| Over 8 to 11 in | 0.016 in (0.41 mm) | 0.020 in (0.51 mm) |
| Over 11 to 24 in | 0.016 in (0.41 mm) | 0.024 in (0.61 mm) |
| Over 24 to 36 in | 0.020 in (0.51 mm) | 0.032 in (0.81 mm) |
| Over 36 in | 0.024 in (0.61 mm) | 0.040 in (1.02 mm) |
Almexa rolls from 0.0177 in (0.45 mm): it covers 0.020, 0.024, 0.032, 0.040 and 0.050 in. Not yet 0.016 in (0.41 mm), the most common gauge on small pipe with rigid insulation: with the equipment being installed at the plant the minimum will drop to 0.012 in (0.3 mm) by the end of 2027. Outdoors, over non-rigid insulation, NIA recommends at least 0.024 in (Mechanical Insulation Design Guide).
Which alloy and temper should I order?
| Use | Alloy and temper | At Almexa |
|---|---|---|
| Pipe and equipment jacketing (ASTM C1729 Grade 1) | 3003 or 3105-H14 | Yes, 0.0177 to 0.148 in, up to 48 in wide |
| Heavy duty, from 0.032 in (Grade 2) | 3003 or 3105-H12 | Yes, same range |
| Elbows and heavily formed parts (Grade 3) | 1100-O | Yes, same range |
| Box-rib sheet for tanks | 3004 | Yes, the flat sheet; the ribbing is done by the forming shop |
Grades and tempers: Johns Manville, metal jacketing installation guide, April 23, 2024. The US government guide specification UFGS 23 07 00 (August 2024) calls for 3003, 5005 or 3105 in H14 or H16 temper. Almexa tempers: 3003 and 3105, O, H1X and H2X; 1100, O to H18; 3004 and 5052, O, H32, H34 and H36 (technical sheet, October 2026).
What Almexa ships and what it does not
- Plain coil, strip and sheet, mill finish, with a mill test report per lot.
- No moisture barrier (polyfilm or polykraft): the jacketing fabricator laminates it onto the plain coil.
- Stucco embossing and corrugation are done by the forming shop.
- Not yet 0.016 in (0.41 mm), and no painted sheet.
Aluminum or stainless steel jacketing?
Aluminum is light, easy to form and costs less than stainless; its emittance ranges from 0.04 new to about 0.1 oxidized. It melts at 660 °C (1,220 °F), so where the project calls for fire resistance, or chemicals or chlorides attack it, 304 or 316 stainless is specified (Insulation Outlook, National Insulation Association, January 2006).
Format: coil for jacketing fabricators
Jacketing fabricators sell rolls 36 and 48 in wide in gauges from 0.016 to 0.050 in (RPR Insul-Mate catalog) and buy their aluminum coil from rolling mills (ITW, 2015). Almexa ships coil 6.30 to 48 in wide with a 20 in (508 mm) inside diameter and a 39 to 46 in outside diameter; strip slit to your width on its 3 slitting lines; and sheet 24 to 144 in long.
What to send for a quote
- Alloy and temper, or the ASTM C1729 grade your project calls for.
- Thickness, in inches or millimeters.
- Coil width or sheet size.
- Inside diameter and maximum coil weight your line takes.
- Tons per month, and for pipe jacketing, who laminates the moisture barrier.
Product sheets, guides and tools
- Aluminum coil 0.0177 to 0.148 in, up to 48 in wide
- Aluminum sheet and plate
- Aluminum strip slit to your width
- Aluminum for construction
- 3003 aluminum
- 3105 aluminum
- 1100 aluminum
- Aluminum gauge converter
- Quote coil for insulation jacketing the form already carries the product
Sources
- ASTM C1729, Standard Specification for Aluminum Jacketing for Insulation (public summary, C1729-26) scope and classification
- Jim Young, ASTM Standards for Metal Jacketing, National Insulation Association, April 1, 2017 grades, types, classes and moisture barrier
- ITW Insulation Systems, aluminum roll jacketing data sheet, 2015 minimum thickness by diameter and coil sourcing
- Johns Manville, Metal Jacketing Installation Guide, April 23, 2024 alloy and temper by grade
- National Insulation Association, Mechanical Insulation Design Guide, Materials and Systems outdoor gauge
- USACE, NAVFAC and AFCEC, UFGS 23 07 00, August 2024 alloys and tempers for US government work
- Gary Whittaker, Industrial Insulation Jacketing, Insulation Outlook, January 1, 2006 aluminum or stainless
- NOM-009-ENER-2014, energy efficiency of industrial thermal insulation systems, Mexico, August 8, 2014 Mexican standard
Commercial jacketing formats: RPR Insul-Mate catalog. Size ranges and tempers: Almexa technical sheet, October 2026. Sources consulted on November 24, 2026.
Frequently asked questions
What thickness of aluminum is used for pipe insulation jacketing?
Per ASTM C1729, from 0.016 in on pipe insulation up to 8 in outside diameter to 0.040 in on diameters over 36 in with non-rigid insulation. Almexa rolls from 0.0177 in (0.45 mm), that is, gauges from 0.020 in up.
3003 or 3105 for insulation jacketing?
Both fall under ASTM C1729 Grade 1 in H14 temper; heavy-duty jacketing from 0.032 in uses H12, and elbows use 1100-O. Almexa makes 3003, 3105 and 1100 from 0.0177 to 0.148 in and up to 48 in wide.
Does Almexa sell aluminum jacketing with a moisture barrier?
No. Almexa ships plain mill-finish coil, strip and sheet. The moisture barrier, stucco embossing and corrugation are done by the jacketing fabricator, who buys the plain coil.
Aluminum or stainless steel jacketing?
Aluminum when you want low weight, easy forming and lower cost. 304 or 316 stainless when the project requires fire resistance, since aluminum melts at 660 °C, or when chemicals or chlorides attack it.